Technical Data

Plant Room Technical Specifications

PhaseThreeThreeThreeThreeThreeThreeThree
Nominal thermal kW rating25 HT253040456075
Product Code
X - H Heating Only
R Reverse Cycle
C Cooling only +
PH250XP250XP300XP400XP500XP600XP750X
MCS ApprovedHeating: BBA0055/34Heating: BBA0055/16
Reverse cycle: BBA0055/24
Heating: BBA0055/17
Reverse cycle: BBA0055/25
Heating: BBA0055/18
Reverse cycle: BBA0055/26
Heating: BBA0055/19
Reverse cycle: BBA0055/27
NoNo
Performance data - rated heating output at B0/W35 BS EN14511
Power consumption6.446.589.712.815.919
Co-efficient of Performance*4.174.084.194.174.173.984.05
Immersion heater outputKensa Heat Pumps do not feature back-up electric immersion heaters**
Brine (primary): Based on 0°C in / -4°C
Design flow rate kg/min82.468.587.4105.6135.2167.8207.4
Pressure drop kPa at design flow rate12.611.11723.625.221.831.7
Max inlet temperature °C15151515151515
Min temperature °C (outlet)-5 (at standard settings)-5 (at standard settings)-5 (at standard settings)-5 (at standard settings)-5 (at standard settings)-5 (at standard settings)-5 (at standard settings)
Heating water (secondary): Based on 30°C in / 35°C out
Design flow rate l/min12074.795112147.6183.5224.9
Pressure drop kPa at design flow rate7.271312.216.919.51725.5
Max flow temperature °C***Up to 65?C depending on application505050505050
Electrical values at B0/W35
Rated voltage400V / 50Hz
Power supply rating amps40323240506370
Rated current (max) amps32222532415263
Typical running current at B0/W35 amps15.3131418232936
Starting current amps ****54577589101112140
Refrigerant circuit
Process mediumR134aR407CR407CR407CR407CR407CR407C
Fill volume kg32.252.533.753.755.5
Compressor typeScrollScrollScrollScrollScrollScrollScroll
Dimensions
H X W X L (mm)1750 x 800 x 9001750 x 800 x 9001750 x 800 x 9001750 x 800 x 9001750 x 800 x 9001750 x 800 x 9001750 x 800 x 900
Dry weight kg280200250280300350380
Operating pressure
Brine circuit min (primary) bar g0.30.30.30.30.30.30.3
Heating water circuit min (secondary) bar g0.30.30.30.30.30.30.3
Low pressure reset bar g1.81.81.81.81.81.81.8
Connection sizes
Primary IN and OUT PN10/16DN40DN40DN40DN40DN40DN40DN40
Heating flow and return PN10/16DN40DN40DN40DN40DN40DN40DN40
Performance (based on Average Climate) @ 35°C
ErP ratingA+A+A+A+A+N/AN/A
SCOP*****3.913.753.853.823.75N/AN/A
Seasonal space heating energy efficiency148%142%142%145%142%N/AN/A
Performance (based on Average Climate) @ 55°C
ErP ratingA+A+A+A+N/AN/AN/A
SCOP*****3.33.043.133.16N/AN/AN/A
Seasonal space heating energy efficiency124%114%117%118%N/AN/AN/A
Sound Power Level
Sound Power Level (dB)6868687171N/AN/A
ᵻ Units are currently being ErP tested and will be available when complete.
^The 45kW Plantroom produces above 50kW at a ground temperature of 0°C and load temperature of 35°C.
+ Cooling only units are not MCS approved.
* The COP figure quoted excludes the water pump electrical input and is calculated according to EN14511.
** In-built immersion heaters will increase running costs and CO2 emissions as they use direct electricity, because of this Kensa heat pumps do not include them.
*** By increasing the flow temperature from the heat pump the efficiency of the unit will drop and the COP decreases.
**** The starting currents are per phase. For full details on how the starting currents are calculated please contact Kensa.
*********The SCOP figure quoted is calculated as per EN14825.
Note i): Design flowrates and pressure drops are based on a ground temperature of 0°C and –4°C and a load temperature of 30°C and 35°C.
Note ii): The P500X unit is classed as a Low Temperature Space Heater as per the ErP regulations.