Technical Data

Evo Series Technical Specifications

PhaseSingleSingleSingleSingle
Nominal thermal kW rating791317
Part NumberK070-S1HK090-S1HK130-S1HK170-S1H
MCS ApprovedBBA 0055/36BBA 0055/37BBA 0055/38TBC
Performance data - rated heating output at B0/W35 BS EN14511
Power consumption1.72.163.2TBC
Co-efficient of Performance*4.424.254.033.96
Immersion heater outputKensa heat pumps do not feature back-up electric immersion heaters**
Brine (primary) based on 0°C in / -4°C out
Design flow rate kg/min23.327.437.9TBC
Pressure drop kPa at design flow rate71117.1TBC
Max inlet temperature °C15
Min temperature °C (outlet)-5 (at standard settings)
Heating water (secondary) based on 30°C in / 35°C out
Design flow rate l/min21.826.938.3TBC
Pressure drop kPa at design flow rate3.984.9510.1TBC
Max flow temperature °C***62
Electrical values at B0/W35
Rated voltage220 - 240V / 50 - 60 Hz
Power supply rating amps25253250
Rated current (max) amps17.421.832.746
Typical running current at B0/W35 amps8.812.716.421
Starting current amps****18.228.741.355
Refrigerant circuit
Process mediumR407C
Fill volume kg222.2TBC
Compressor typeScroll
Dimensions
H X W X L (mm)1160 x 555 x 575
Dry weight kg153154
167TBC
Operating pressure
Brine circuit min (primary) bar gSettable at commissioning
Heating water circuit min (secondary) bar gSettable at commissioning
Low pressure reset bar gSettable at commissioning
Connection sizes
Primary IN and OUT (speedfit) mm28
Heating flow and return (speedfit) mm28
Performance (based on Average Climate) at 35°C
ErP ratingA++A++A++A++
SCOP*****4.694.474.294.26
Seasonal space heating energy efficiency180%171%164%TBC
Performance (based on Average Climate) at 55°C
ErP ratingA++A++A++A+
SCOP*****3.673.393.463.29
Seasonal space heating energy efficiency139%127%130%TBC
Sound Power Level
Sound Power Level (dB)50.954.653.8TBC
Figures shown for the 17kW Evo are indicative and subject to final testing and MCS accreditation in summer 2018.
* The COP figure quoted is calculated as per EN14511.
** In-built immersion heaters will increase running costs and CO2 emissions as they use direct electricity, because of this Kensa heat pumps do not include them.
*** By increasing the flow temperature from the heat pump the efficiency of the unit will drop and the COP decreases.
**** Kensa Evo heat pumps incorporate smart starts as standard to limit the starting current of the compressors. For full details on how the starting currents are calculated please contact Kensa.
****The SCOP figure quoted is calculated as per EN14825.
Note: Design flowrates are for a ground temperature of 0 and –3oC and a load temperature of 30oC and 35oC